The CVT-OPTW is designed to provide isolation between different Wiegand signal
sources.
The CVT-OPTW allows multiple readers and panels to be connected together
The CVT-OPTW also allows systems with different voltage levels to be electrically
connected together.
Data 1 IN
Ground
Data 0 IN
Data 1 OUT
Data 0 OUT
Pullup +5V
Pullup +5V
+5 VDC
Ground
J1 Connector
Gnd - Input Ground
Data 0 In - Wiegand Data Input 5- 24 VDC
Data 1 In- Wiegand Data Input 5 - 24 VDC
J2 Connector
5 vdc - Input - regulated 5 vdc @ 30ma
Pullup +5V - Connection to pullup resistor 1k @ 5VDC
Data 0 OUT - Open collector Wiegand data output
Pullup +5V - Connection to pullup resistor 1k @ 5VDC
Data 1 OUT - Open collector wiegand data output
Gnd - Output ground
Notes:
1. Input Ground and Output Ground are electrically isolated.
2. +5VDC (Regulated) is required to operate converter.